"<table class=\"table jumo-table\" dir=\"ltr\"><colgroup><col><col></colgroup><tbody><tr dir=\"ltr\"><th dir=\"ltr\" ><p class=\"\" dir=\"ltr\"><span >Controller type</span></p></th><th dir=\"ltr\" ><p class=\"\" dir=\"ltr\"><span >Parameter</span></p></th></tr><tr dir=\"ltr\"><td dir=\"ltr\" ><p class=\"\" dir=\"ltr\"><span >2-tilstandscontroller ON/OFF-funktion</span></p></td><td dir=\"ltr\" ><p class=\"\" dir=\"ltr\"><span >Pb1, dt, rt, Cy1, df</span></p></td></tr><tr dir=\"ltr\"><td dir=\"ltr\" ><p class=\"\" dir=\"ltr\"><span >3-tilstandscontroller</span></p></td><td dir=\"ltr\" ><p class=\"\" dir=\"ltr\"><span >Pb1, Pb2, dt, rt, Cy1, Cy2, df</span></p></td></tr><tr dir=\"ltr\"><td dir=\"ltr\" ><p class=\"\" dir=\"ltr\"><span >Proportional controller</span></p></td><td dir=\"ltr\" ><p class=\"\" dir=\"ltr\"><span >Pb1, dt, rt, df</span></p></td></tr></tbody></table>"
Så snart autotuning startes med tasten »Exit« (hold nede i 2 sekunder), forsøger controlleren at bestemme procesens tidsrespons ved at anvende trinændringer i manipuleringsvariablen. Autotuning evaluerer udviklingen af procesværdien som følge af disse ændringer i manipuleringsvariablen og beregner controllerparametrene. Under autotuning blinker »tune« i det nederste display. Når autotuning-proceduren er afsluttet, holder »tune« op med at blinke. Varigheden af autotuning-proceduren afhænger af tidsresponsen for den kontrollerede proces. Hvis processen reagerer relativt hurtigt på ændringerne i manipuleringsvariablen, kan autotuning være afsluttet på få sekunder eller minutter. Ved langsomme processer kan autotuning tage en halv time eller længere.